Buy Edwards SIGA-CC1 Control Module at the best price with intelligent device control, electronic addressing, continuous supervision and reliable integration for advanced fire alarm systems.
The Edwards EST SIGA-CC1 Control Module is an intelligent addressable control module designed to provide reliable monitoring and control of notification appliances, relays and auxiliary devices within Edwards Signature Series fire alarm systems. Engineered for seamless integration with Edwards EST fire alarm control panels, the SIGA-CC1 enables efficient activation of connected devices while delivering accurate status reporting and system supervision.
The SIGA-CC1 Control Module functions as a single-input signalling control module, allowing fire alarm systems to control external devices such as horns, strobes, speakers, door holders, dampers, relays and other life safety equipment. Through intelligent communication with the fire alarm control panel, the module ensures that connected devices respond immediately during alarm, supervisory or emergency events.
Featuring electronic addressing technology, the SIGA-CC1 eliminates manual addressing switches and simplifies installation. Automatic device mapping helps reduce commissioning time while improving system accuracy. Continuous communication with the fire alarm panel ensures that device status, faults and wiring conditions are constantly monitored for enhanced reliability.
The module incorporates built-in diagnostics and advanced supervision features that help identify wiring issues, open circuits and device faults before they impact system performance. This proactive monitoring helps reduce maintenance costs and ensures ongoing compliance with fire safety standards.
The Edwards EST SIGA-CC1 Control Module is ideal for commercial buildings, hospitals, hotels, educational institutions, industrial facilities, retail complexes, and critical infrastructure applications. Its flexible control capabilities make it an essential component in modern addressable fire alarm systems where reliable activation and monitoring of field devices are required.
Whether used in new installations or retrofit projects, the SIGA-CC1 delivers dependable device control, simplified system management and enhanced life safety performance.
| Parameter | Value |
| Operating voltage range | 15.20 to 19.95 VDC |
| Current – Standby | 310 µA |
| Current – Activated | 135 µA |
| Maximum line impedance | Refer to the control panel installation manual |
| Ground fault impedance | 10 kΩ |
| Output ratings (24 VDC) | 2 A |
| Output ratings (25 VRMS audio) | 50 W |
| Output ratings (70 VRMS audio) | 35 W |
| EOL resistor value | 47 kΩ |
| Circuit resistance | Refer to the control panel installation manual |
| Circuit capacitance | 0.1 µF max. |
| EOLR | 47 kΩ (P/N EOL-47) |
| Signaling line circuits | Class A, Style 6 or Class B, Style 4 |
| Telephone riser circuits | Class B, Style 4 |
| Notification line circuits | Class B, Style Y |
| LPCB/CPR electrical box requirements | Plastic box with cover plate, no gaps or unused holes |
| Minimum electrical box size (W × H × D) | 3.5 × 3.5 × 1.5 in. (85 × 85 × 38 mm) |
| Compatible electrical boxes | 2-1/2 in. (64 mm) deep dual-gang box; 4 in. square box 1-1/2 in. (38 mm) deep with dual-gang cover |
| Wire sizes | 12 to 18 AWG (1.0 to 4.0 mm²) |
| Operating temperature | 32 to 120°F (0 to 49°C) |
| Relative humidity | 0 to 93%, noncondensing |
| Storage temperature range | −4 to 140°F (−20 to 60°C) |
https://innxeon.com