Support for up to 8 loops and more than 2000 addressable devices. It provides smart detection, easy setup, and smooth integration with building management systems.
The GST-IFP8 Addressable Fire Alarm Control Panel is a high-performance fire detection system designed to protect large and complex infrastructures. Built with state-of-the-art addressable technology, this smart control panel offers excellent scalability, precise monitoring, and meets international fire safety standards, including EN54-2 and EN54-4.
With support for up to 8 Class A loops and over 1,900 addressable devices, the GST-IFP8 is perfect for commercial buildings, data centres, industrial facilities, hospitals, and critical infrastructure. The system can handle up to 999 detection zones, with 140 zones featuring dedicated alarm and fault LEDs for quick identification and faster responses. The panel has a 15×40 character LCD and 17 LED indicators that provide real-time system status, fault alerts, and device diagnostics. Its non-volatile memory ensures that important configuration and event data are saved even during unexpected power failures.
Designed for full compatibility with GST’s EN-certified addressable detectors and modules, the GST-IFP8 allows for easy integration and operational flexibility. It features multiple communication interfaces, including RS232 and dual RS485 ports, enabling communication between the panel and PC, system networking, and repeater connectivity for better coverage. From fire alarm announcements to smart event logging and centralized control, the GST-IFP8 sets a new standard in modern fire safety technology. Whether you are protecting a high-rise, a manufacturing facility, or a mission-critical data centre, this panel offers reliability, scalability, and intelligent protection when you need it most.
| Primary Supply: | 220/230VAC,50/60Hz |
| AC Current: | 1A |
| Standby Power: | 38AH/24VDC |
| Max. Battery Resistance: | 0.7Ω |
| Loop Capacity: | 2-8 Loops |
| Zone Capacity: | 999 (140 with individual alarm/fault indicator and label) |
| Device Loop: | 242 addresses per loop |
| Printer: | Thermal ASCll code printer |
| Display: | 15(lines)x40(characters), LCD |
| Network (RS485): | Class A, Max. 32 panels (by card) |
| Network (CAN): | Class A, Max. 100 panels (by card) Class B, Max. 240 panels (by card and other accessories) |
| PC Port: | RS232/USB interface (by card) |
| Protection: | |
| Operating Environment: | 0°C~+40°C ≤95%, non-condensing |
| Dimensions: | 484mm(W)x850mm(H)x191mm(D) |